Saturday, June 20, 2009

MEEB: Hot Water Boilers

MEEB: Hot Water Boilers

System Components: A fuel, a heat source, a "mover (fan or pump), a distribution system, a heat exchanger or terminal within the space and a control system

Rated according to heating capacity by several different categories

Heating capacity = rate of useful heat output with the boiler operating under steady-state conditions
- expressed in Mbh (1000 btu/h)
- AFUE = Annual fuel utilization efficiency is 100% minus the losses up the stack during both the on and off cycles and losses due to infiltration of outdoor air to replace the air used for combustion adn draft control.
- net I = B = R rating is b\published by the Hydronics Institute Division of GAMA

Boiler selection based on matching the calculated heat loss of the structure to be heated.

Types:
- Oil fired steel boiler
- Gas fired cast iron hot water boiler
- Oil fired, cast iron hot water boiler.

MEEB: Roof Color

MEEB: Roof Color

Roof color is the first step toward energy savings.

White or near white roofs are preferred.

The higher the emissivity, the faster a roof surface reradiates its heat to the sky.

Compare solar absorptance, albedo (overall solar reflectance), and emissivity for selection of the optimum materials.

Combination of high albedo and high emissivity resists solar heat gain most effectively.
(which also promises to reduce the heat island effect in urban areas.)

A solar reflectance index (SRI) allows quick comparisons between roofing products
Lower SRI is worse than higher SRI
0 = 5% albedo and 90% emittance (close to black asphalt shingles)
100 = 80% albedo and 90% emittance (close to EPDM white single ply roofing)




MEEB: Compressive Refrigeration Cycle

MEEB: Compressive Refrigeration Cycle

Liquefaction and evaporation of a refrigerant that gives off and absorbs heat.

Heat it gives off is disposed of, heat it absorbs is from circulated water, known as chilled water.

Chilled water is the medium for the subsequent cooling processes.

Refrigerants are a gas at normal temperatures and pressures which are compressed and liquefied to be able to be used as heat absorbers.

System consists of refrigerant within a closed loop pipe system with a low(evaporator) and high(condenser) pressure side
A compressor and expansion valve separates the two sides.

Compressor condenses the refrigerant which passes through the cool condensing water

cool condensing water removes latent heat from the pressurized gas turning the refrigerant into a liquid form.

The condensed liquid is released through the expansion valve into the evaporator, instantly returning to the gaseous state
The change back to gas requires heat and thus it is absorbed from water running over the piping,
the water in turn is chilled and is used for cooling air.

The system can be reversed to create a heat pump instead of cooling.


Friday, June 19, 2009

MEEB: Moving Walks and Ramps

MEEB: Moving Walks and Ramps

Moving horizontal, or horizontal and vertical transportation
Moving walk = Level or Incline not exceeding 5 degrees
Moving ramp = Incline up to but not exceeding 15 degrees
Both are physically the same type of machine (similar components to escalators)

Moving walks (aka Autowalks)
Principal uses:
1. eliminated and/or accelerate burdensome walking
2. eliminate congestion
3. force movement
4. easily transport large, bulky objects

- Common in airports, due to long distances and heavy luggage
- Store parking can be further way with their implementation
- avoiding congestion is key requirement for their use

Moving Ramps
Principal uses:
1. Move persons and wheeled vehicles vertically
2. move persons who lack agility required to use an escalator
3. vertically move large bulky objects

- used in multilevel stores where escalators are not feasible for shopping cart users


Components
For both types, all components are same as escalator with the exception of a flattend pallet in place of a step.

MEEB: Vertical Transportation: Escalator Fire Protection and Lighting

MEEB: Vertical Transportation: Escalator Fire Protection and Lighting

Fire Protection
Four methods: rolling shutter, smoke guard, spray nozzle curtain and sprinkler vent
One of which is required by code when more than two floors are pierced.

Fire shutter = a horizontal rolling metal shutter that prevents draft and spread of fire upward through escalator wells, activated by temp. and smoke detectors

Smoke guard = fireproof baffles surrounding the wellway extending downward about 20 inches from the ceiling. Standard sprinkler heads release a curtain of water
vertical shields between adjacent sprinklers ensure that spray from one will not cool the nearby thermal fuses preventing them to open.

Spray nozzle curtain of water = similar to smoke guard, closely spaced high velocity water nozzles form a compact water curtain to prevent smoke and flames from rising through the wellways.
Automatic thermal or smoke relays open all nozzles simultaneously.

Sprinkler vent = Fresh air intake housed on the roof contains a blower to drive air downward through the escalator floor openings while exhaust fan on the roof creates a strong draft upward through an exhaust duct.
this duct draws air from the separate ducts just under the ceiling of each moving stairway floor opening drawing the smoke out through an automatic damper.
spray nozzles are also located at ceiling near stairways.


Lighting
special emphasis on lighting the comb plate.
See other lighting notes in general requirements post.

MEEB: Vertical Transportation: Escalator Safety Features

MEEB: Vertical Transportation: Escalator Safety Features

- Handrails and steps travel at exactly same speed to assure steadiness and balance and to aid stepping on or off the comb plates
- Steps are large and steady and are designed to prevent slipping
- Step design and step leveling with the comb plates at each landing prevent tripping upon entering or leaving the escalator. Accomplished with two or three horizontal trad at each end of the escalator.
- Balustrade is designed to prevent the catching of passengers' clothing or packages. Close clearances provide safety near the comb plates and step treads.
- Adequate illumination provided by the building at all landings, comb plates and completely down all stairways. Some units have built-in lighting.
- Automatic service brake will bring to a smooth stop if
a. drive chain or the step chain is broken or abnormally stretched
b. a foreign object is jammed into the handrail inlet, between the skirt guard and step or between steps, causing them to separate.
c. A power failure occurs
d. the emeregency stop button is operated ( on is located at each end of the escalator)
e. any of the fire safety system devices operates
f. a tread sags, rises or breaks
g. a drive motor malfunction occurs
- in case of over or underspeed, an automatic governor shuts down the escalator, prevents reversal of direction and operates the service brake.

MEEB: Vertical Transportation: Escalator Design

MEEB: Vertical Transportation: Escalator Design

First operated in 1900 at the Paris Exposition

Two types of arrangement, criss cross and parallel arrangements
criss cross = from side elevation the up and down escalators form a cross or X shape
it has two modes, spiral and walk-around which applies to whether you can board the next escalator up adjacent to the landing or if you have to walk-around to the opposite end
Most common of the two
takes up less room
Parallel = escalators face in same direction, from side elevation, up and down escalators are in line with each other (one is hidden by the other)
two modes, stacked (walk-around) and spiral
requires more floor space, used less often

General escalator guidelines
Centrally locate in main line of traffic
Mark escalator destinations clearly to avoid confusion of traffic.
1. provide well marked escalators with sufficient traffic carrying capacity.
2. provide collecting space at intermediate landings so that pressure can be relieved
3. provide a physical divider at intermediate landing turnaround points that guides riders away from the discharge point and provide adequate space (and time) for riders either to leave at that level or to follow the guide around and continue the trip.
4. Provide a slight setback for the next escalator so that the necessary 180 deg turn can readily be negotiated.

Newels = moving rail extensions at top and bottom landings
8 feet past landing for 32 inch units
10 feet past landing for 48 inch units

Escalators are reversible to accommodate traffic requirements

Standard designs
Inclination = 30 degrees from horizontal in all of United States
Vertical clearance = 7 feet clear
maximum linear speed = 125 fpm (per ANSI/ASME 17.1, verify)
Industry standard linear speed = 100 fpm
Size (between balustrades) = 32" and 48"
Width (refers to tread width, typically referred to as tread depth in stair design) = 24" tread for 32" size, 40" tread for 48" size

Approximate Maximum Rises:
unit size type supports max. rise
32" standard, supported at ends only = 24 feet
48" standard, supported at ends only = 16 feet

32" standard, supported at ends & center = 30 feet
48" standard, supported at ends & center = 20 feet

32" heavy, supported at ends only = 24 feet
48" heavy, supported at ends only = 18 feet

32" heavy, supported at ends & center = 40 feet
48" heavy, supported at ends & center = 20 feet
(note:these are general and vary with manufacturer)


Special designed units available up to about 60 foot rises
BUT
as rise increases, loads on all drive components including chains and sprockets increase sharply
heavier equipment requires increased truss width, wellway size and balustrade decks.
Rises above 25 to 30 feet (depending on unit width) drive motor won't fit inside the truss and requires a separate machine room below the truss.


MEEB: Vertical Transportation: Elevators - Freight, Observation, Inclined, Rack and Pinion

MEEB: Vertical Transportation: Elevators - Freight, Observation, Inclined, Rack and Pinion

Freight
self explanatory, will not cover

Observation
glass encased, will not cover

Inclined
for use at a slant, running on rails pulled by traction cable

Rack and Pinion
rotating cogged wheel pinion attached to vertical rack.
Pinion rotation force cab up and down
simple, safe, unlimited rise
indoor and outdoor
primarily for industrial use

MEEB: Vertical Transportation: Hole-less and Roped Hydraulic Elevators

MEEB: Vertical Transportation: Hole-less and Roped Hydraulic Elevators

Hole-less Hydraulic Elevators
Used where drilling a plunger hole presents difficulties.
Uses a telescoping plunger, single jack or dual jack (used more often) mounted to sides of car
require more maintenance, but easier to get to
dual jack, creates less smooth ride causing a degree of jerk.


Roped Hydraulic Elevators
Simpler than telescoping
uses only a single moving jack section compared to two or three.
by using 2:1 roping meaning car travels twice as far as the piston
Accomplished by passing rope over a pulley in the piston crosshead.
One end of rope attached to fixed point in pit below car, other end attached to base of car
Piston lifts the crosshead and in turn lifts the car
Most common choice for low rise, light to medium duty hydraulic.
Roped, so equipped with slack rope safety in addition to other safeties.

MEEB: Vertical Transportation: Hydraulic Plunger Type Elevators - Plunger Type

MEEB: Vertical Transportation: Hydraulic Elevators - Plunger Type

Raised and lowered by means of movable rod (plunger) rigidly fixed to the bottom of the elevator car.
More inexpensive than Traction = No cables, drums, traction motors, elaborate controllers, safety devices or penthouse equipment required

Seed & rise = low speed - 200 fpm & low-rise - up to 65 ft

Hydraulic oil used, powered by an oil pump.

No overhead machine room required (a big plus)

Additional advantages over traction units:
Load is carried by ground rather than structure at top of shaft
Smaller hoistway due to absence of counterweight and its guide rails
cars lower manually by operation of oil valves (good if control equip. or power fails)
No limit to load that can be lifted

Inherent disadvantages
- operating expense
- not counterweight creates necessity of large motor to drive oil pump and all energy is lost in heat.
- limited to low rise, low speed applications, four story max.
- ride quality inferior to traction
- temp of pump and oil storage tank must be controlled to keep oil viscosity at acceptable levels
- high inrush of current taken by pump each time ti travels up requires a "stiff" power supply to avoid line voltage fluctuations.
- Pump, motor and piping can be noisy, mitigation by locating pump mechanism up to fifty feet from the elevator shaft

Plunger type have been used less due to oil seepage into the ground, Hole-less and roped Hydraulics have come into more common use in response.


MEEB: Vertical Transportation: Elevators - Fire Safety

MEEB: Vertical Transportation: Elevators - Fire Safety

Most fire codes require the following occur in event of a fire emergency:
1. all cars close their doors and return, non stop to lobby or other designated floor, where they park and stay with doors open
Afterward they only work manually by fireman's key
2. All car and hall calls are canceled and call registered lights and direction arrows extinguished
3. fire emergency light or message panel in each car is activated to inform passengers of nature of the alert and that cars are returning to designated terminal.
4. Door sensors and in car emergency stop switches are deactivated.
5. Traveling cars stop at the nearest landing without opening doors, then proceed to the designated terminal.


MEEB: Vertical Transportation: Elevators: Accessibility Requirements

MEEB: Vertical Transportation: Traction Elevators: Accessibility Requirements

Physical limitations (Handicaps) addressed:
Ambulation
Sight
Hearing

General requirements:
Wheelchair
36" min. door opening, 42" recommended
delayed door closing
detection beams that open door without contact (beam)
car dimensions allowing a turning wheelchair
buttons and emergency controls within easy reach
appropriate finishes

Sight / Hearing
Audible signals (as well as easily seen and recognized visual ones) in the car and at landings
call registration indicators
car approach indicator
car landing indicator
direction of travel indicator
floor indicator
car position indicator, etc.
braille at call buttons
large recognizable symbols next to floor buttons
call button indicate call has been placed

Code
self leveling tolerance = 1/2"
Hall Call button = +42" aff
Hall lantern = visible and audible signal indicating car that is responding to call button
sound once for up direction, twice for down OR say "up" or "down"
Mount min. 72" aff
Tactile Floor indicators = in raised lettering and braille, located 60" aff on all floors at both jambs, 2" high characters
Door protective and reopening device = sense and reopen doors without contact, sensing at heights of 5" and 29", reopening at a min. of 20 seconds
door delay for car calls = min. of 3 seconds for door to remain open
illumination = min. of 5 footcandles
Car controls = Buttons at least 3/4" in smallest dimension, raised or flush
Tactile braille and visual control indicators at each button
Main entry floor designated by a raised start at the left of the floor designation.
raised designations to the left of the buttons.
Height = All buttons shall be no higher than 54 inches above finish floor for side approach, 48 inch max. for front approach.
Emergency controls = grouped below controls panel, no less than 35 inches above finish floor
Car position indicators = required above control panel or over the door, shows position of the elevator in hoistway (floor)
floor being passed is shown on position indicator as well as an audible tone when passed
Emergency communications = highest operable part shall be max. 48 inches aff, cord from handset at least 29 inches.